Series: Legacy Lighting Relays That Refuse to Die
If you’ve ever opened a lighting control panel in a school, hospital, or older commercial building and seen a row of identical rectangular relays with low-voltage control wiring, there’s a good chance you were looking at GE RR7 relays.
They’re not flashy. They don’t have screens, software, or IP addresses. But they’ve been controlling lighting in commercial buildings for decades — and many of them are still doing it every day.
So what exactly is an RR7, how does it work, and why do so many facilities still rely on them?
The GE RR7 is a mechanically latched, low-voltage lighting control relay designed for commercial and institutional lighting systems.
Its job is simple:
-
Use a momentary low-voltage signal (typically 24V)
-
Switch a line-voltage lighting circuit
-
Stay ON or OFF without continuous control power
That last point is what made the RR7 different — and why it became so widely used.
Once the relay changes state, it remains mechanically in that state until it receives the opposite command.
How the GE RR7 Relay Works
RR7 relays are built around a clean separation of control and load.
Low-Voltage Control Side
-
Operates on momentary 24V AC pulses
-
Uses simple pushbuttons instead of line-voltage switches
-
Allows multiple control points for the same lighting circuit
-
Makes long control wire runs practical and safe
Line-Voltage Load Side
-
Switches 120V or 277V lighting circuits
-
Rated for commercial lighting loads
-
Electrically isolated from the control wiring
-
Contacts are rated 20A @ 120/277 VAC
The Latching Mechanism
Inside the RR7 are two coils:
-
One coil turns the lights ON
-
One coil turns them OFF
A brief pulse energizes the appropriate coil, and a mechanical latch holds the contacts in position. No holding current is required.
If power is lost, the relay stays exactly where it was.
A Short History of the GE RR7 Relay
The RR7 didn’t become common by accident — it solved real problems at scale.
RR7 Timeline
-
1950s–1960s – GE introduces low-voltage relay lighting systems to reduce wiring complexity and energy use.
-
1970s–1980s – RR7 relays become standard in schools, hospitals, offices, and government buildings.
-
1990s – Systems expand to include time clocks, photocells, and early automation.
-
2000s – Manufacturers shift toward digital lighting controls; RR7 systems remain in service.
-
Today – Thousands of RR7 panels are still operating, supported by replacement and refurbished relays.
The RR7 wasn’t replaced because it failed — it was replaced because the industry moved toward software.

Where You’ll Commonly Find RR7 Relays
RR7 systems are still common in:
-
Schools and universities
-
Hospitals and medical facilities
-
Office buildings
-
Industrial plants
-
Hotels and convention centers
-
Government and municipal buildings
In many cases, the lighting panel has never been upgraded — because it hasn’t needed to be.
Common GE RR7 Failure Points (What Electricians Actually See)
RR7 relays have a reputation for reliability, but nothing lasts forever. When they do fail, the symptoms are usually familiar.
1. One Coil Stops Working so the Relay is stuck in One Position
-
ON works, OFF doesn’t (or vice versa)
-
Lights won’t shut off or won’t turn on
-
Common in very old relays or where the control voltage is unstable
(Test resistance with a multimeter)
2. Worn or Pitted Contacts
-
Years of switching lighting loads take a toll
-
Can cause intermittent operation or flickering
(Replacement may be due) -
More noticeable in high-use areas
3. Mechanical Latch Wear
-
Less common, but possible after decades
-
Relay may not stay latched consistently
-
Typically signals end-of-life
4. Control Circuit Issues (Often Blamed on the Relay)
-
Loose low-voltage connections
-
Failed pushbuttons or time clocks
-
Many “bad relays” turn out to be control problems upstream
(Check control wiring and transformer output.)
5. Obsolescence, Not Failure
-
Relay works fine, but a replacement is needed fast
-
Facility doesn’t want to redesign the system
-
Drop-in replacements become critical
Why Facilities Keep RR7 Systems Instead of Replacing Them
Replacing an RR7 system usually means:
-
Rewiring control circuits
-
Replacing panels
-
Updating drawings
-
Recommissioning lighting zones
-
Training maintenance staff
For many facilities, that cost makes no sense when the existing system is still reliable.
RR7 systems offer:
-
Proven long-term reliability
-
Extremely low energy consumption
-
Simple troubleshooting
-
No software, licensing, or network dependency
Why the GE RR7 Relay Still Matters
The GE RR7 relay is a reminder that not all legacy equipment is obsolete — some of it is just well-engineered.
As manufacturers discontinue older components, the challenge isn’t understanding how RR7 systems work — it’s keeping them running.
That’s why tested surplus and refurbished RR7 relays continue to matter to electricians, facility managers, and maintenance teams who deal with real buildings, not theoretical upgrades.
If your work includes maintaining or upgrading breaker panels, you may also find this related guide helpful: Shield Your Power: Why Motor Circuit Protectors Are the Unsung Heroes of Industrial Reliability
For more real-world insights and professional discussions around remote switching, low-voltage control systems, and relay applications like the RR7, check out the ElectricianTalk.com articles section. It’s a resource-rich space where industry veterans share practical knowledge and installation stories—perfect for expanding your expertise beyond product specs.
References / Bibliography:
-
GE Lighting Controls – Technical Specs and Manuals (Archived resources via General Electric technical documentation)
-
IEEE Standards on Electromechanical Switching Devices
-
National Electrical Manufacturers Association (NEMA): Guidelines for Remote Switching Devices
-
U.S. Department of Energy: “Low-Voltage Lighting Control Systems” – Facility Management Best Practices
-
Electric Power Research Institute (EPRI): “Legacy Relay Applications in Modern Facilities”
-
NFPA 70 (NEC): National Electrical Code Guidelines on Remote-Control Switching
Use of Original Equipment Manufacturer (OEM) trademarks, names, and logos is for informational and identification purposes only. This does not imply any affiliation, sponsorship, endorsement, or approval by the original equipment manufacturer. CIRCUIT BREAKER SUPERSTORE® is an independent reseller and is not an authorized distributor, affiliate, or representative of any manufacturer. Manufacturer warranties do not apply unless expressly stated. All trademarks and registered trademarks are the property of their respective owners.
📘 Disclaimer
The information in this blog aims to provide general guidance only. Although we strive for accuracy and relevance, this content should not replace professional advice. Therefore, always consult a licensed electrician or qualified expert for recommendations specific to your setup.
CIRCUIT BREAKER SUPERSTORE® does not accept responsibility for actions taken based on this content. To stay safe, always follow local codes and industry best practices.